Outdoor sensor temperature – Active, 0..5 V, 0..10 V, Switch contact
Application/type Outdoor sensor
Purpose Measure values
Measured values temperature
Interface Active, 0..5 V, 0..10 V, Switch contact
Configuration USEapp, uConfig
Sensor SI-Protection against permeation of humidity and mechanical stress (e.g. vibration)
Output voltage 0..10 V or 0..5 V, live-zero configuration via app or uConfig, min. load 10 kΩ
Output switch contact 2x floating contact NO for 24 V ~ or 24 V = / 3 A
Operating range temperature (°C) -20..+70
Operating ranges temperature (°C) -20..+70
Output signal temperature scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, optionally configurable
Accuracy temperature ±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig
Power supply 15..35 V = SELV, 19..29 V ~ SELV
Power consumption max. 2,5 W (24 V =), 4,3 VA (24 V ~)
Material in touch with media Sensor probe, Ø=6 mm, stainless steel V2A (1.4305), length 25 mm, for faster response
Enclosure USE-M, impact- and shock-resistant enclosure with quick-release cover, PC
Colour pure white
Protection (IP) IP65, according to EN 60529
Connection removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², relay max. 1,5 mm²
Delivery content incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories)
Packaging length (mm) 100
Packaging width (mm) 128
Packaging height (mm) 65
Packaging case packaging
Device length (mm) 85
Device width (mm) 93
Device height (mm) 45
Option enclosure LCD 29x35 mm, RGB backlight
- Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::
- If not in Description, Available Upon Request