Differential pressure transducer differential pressure, volume flow, pressure in Pa or inchWC, volume flow in m³/h or cfm, optionally configurable via app or uConfig – RS485 Modbus, 0..5 V, 0..10 V
 
						
			| Application/type | Differential pressure transducer | 
					
			| Purpose | Measure values | 
					
			| Measured values | differential pressure, volume flow, pressure in Pa or inchWC, volume flow in m³/h or cfm, optionally configurable via app or uConfig | 
					
			| Interface | RS485 Modbus, 0..5 V, 0..10 V | 
					
			| Configuration | USEapp, uConfig, jumper, DIP switches | 
					
			| Sensor | piezo measuring element | 
					
			| Output voltage | 2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ | 
					
			| Network technology | RS485 Modbus | 
					
			| Data transmission | RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) | 
					
			| Operating range temperature (°C) | -10..+50 | 
					
			| Operating ranges temperature (°C) | -10..+50 | 
					
			| Operating range humidity | max. 85% rH short term condensation | 
					
			| Operating range pressure | air or other non-flammable/non-aggressive gases, max. 40 kPa | 
					
			| Measuring range pressure | 0..+250 Pa (default setting), 0..+25 | 0..+50 | 0..+100 | 0..+250 | -25..+25 | -50..+50 | -100..+100 | -150..+150 Pa, selectable at the device | 
					
			| Accuracy pressure | ±1 Pa at range <250 Pa, deviation from calibration reference device (calibrator), automatic zero point calibration | 
					
			| Measuring range velocity (ppm) | 0..750.000 m³/h, optionally configurable | 
					
			| Power supply | 15..35 V = SELV, 19..29 V ~ SELV | 
					
			| Power consumption | max. 2,5 W (24 V =), 4,3 VA (24 V ~) | 
					
			| Display | LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig | 
					
			| Enclosure | USE-L, impact- and shock-resistant enclosure with quick-release cover, PC | 
					
			| Colour | pure white, transparent cover | 
					
			| Protection (IP) | IP65, according to EN 60529 | 
					
			| Connection | removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm², pressure connection male Ø=5,0 mm / Ø=6,3 mm, connection tube: PVC, soft | 
					
			| Mounting | surface-mounted flat on base using screws, prepared for mounting on DIN rail TS35 (35x7,5 mm) according to EN 60715 | 
					
			| Delivery content | incl. mounting base enclosure USE-L pure white, incl. mounting set (screws and accessories), incl. pressure connection set and 2 m PVC connection hose | 
					
			| Packaging length (mm) | 152 | 
					
			| Packaging width (mm) | 128 | 
					
			| Packaging height (mm) | 65 | 
					
			| Packaging | case packaging | 
					
			| Device length (mm) | 110 | 
					
			| Device width (mm) | 105 | 
					
			| Device height (mm) | 48 | 
					
			| Notes | output protection circuit (reverse polarity protected) | 
		
        
        
            Standard Manufacturer's Warranty
        
      
         
               - Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::
- If not in Description, Available Upon Request