Duct sensor, Immersion sensor temperature – Active, 4..20 mA
Application/type |
Duct sensor, Immersion sensor |
Purpose |
Measure values |
Measured values |
temperature |
Interface |
Active, 4..20 mA |
Sensor |
SI-Protection against permeation of humidity and mechanical stress (e.g. vibration) |
Operating range temperature (°C) |
0..+250 |
Operating ranges temperature (°C) |
0..+250 |
Output signal temperature |
scaling analogue output, 0..+250 °C |
Operating range temperature enclosure (°C) |
-35..+70 |
Operating range humidity |
max. 85% rH short term condensation |
Accuracy temperature |
±0,2 K (typ. at 21 °C) | ±0,1% of measured value (typ. at 21 °C) |
Power supply |
15..24 V = (±10%) SELV |
Power consumption |
max. 0,5 W (24 V =) |
Material in touch with media |
Sensor probe, Ø=8 mm, stainless steel V4A (1.4571), length 258 mm |
Installation length (mm) |
250 |
Enclosure |
shape B, aluminium |
Protection (IP) |
IP66, according to EN 60529 |
Connection |
cable entry M20 for wire Ø=7 mm, terminal block, max. 1,5 mm² |
Mounting |
when used as duct sensors: please use mounting flange MF8 stainless steel, for use as immersion sensors please use immersion pocket THVA |
Packaging length (mm) |
400 |
Packaging width (mm) |
130 |
Device length (mm) |
78 |
Device width (mm) |
70 |
Device height (mm) |
336 |
Weight (g) |
250 |
Standard Manufacturer's Warranty
- Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::
- If not in Description, Available Upon Request