Pendulum sensor, Room sensor temperature, CO2 – Active, 0..5 V, 0..10 V
| Application/type |
Pendulum sensor, Room sensor |
| Purpose |
Measure values |
| Measured values |
temperature, CO2 |
| Interface |
Active, 0..5 V, 0..10 V |
| Configuration |
USEapp, uConfig, jumper |
| Sensor |
integrated digital temperature transmitter, NDIR (non-dispersive, infrared) |
| Output voltage |
2x 0..10 V or 0..5 V, adjustable via jumper, min. load 10 kΩ |
| Operating range temperature (°C) |
0..+50 |
| Operating ranges temperature (°C) |
0..+50 |
| Operating range humidity |
max. 85% rH short term condensation |
| Measuring range CO2 |
0..2000 ppm |
| Accuracy CO2 |
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
| Power supply |
15..35 V = SELV, 19..29 V ~ SELV |
| Power consumption |
max. 2,5 W (24 V =), 4,3 VA (24 V ~) |
| Material in touch with media |
Sensor head, black, length 126 mm |
| Enclosure |
USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
| Colour |
pure white |
| Protection (IP) |
IP20, enclosure IP65, according to EN 60529 |
| Connection |
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
| Connection cable |
PVC, 0,25 mm², black |
| Length connection wire (m) |
5 |
| Delivery content |
incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories) |
| Packaging length (mm) |
310 |
| Packaging width (mm) |
220 |
| Device length (mm) |
110 |
| Device width (mm) |
105 |
| Device height (mm) |
48 |