Duct averaging sensor temperature – Active, 0..5 V, 0..10 V
Application/type |
Duct averaging sensor |
Purpose |
Measure values |
Measured values |
temperature |
Interface |
Active, 0..5 V, 0..10 V |
Configuration |
jumper |
Output voltage |
0..10 V or 0..5 V, adjustable via jumper, min. load 5 kΩ |
Operating range temperature (°C) |
-30..+80 |
Operating ranges temperature (°C) |
-30..+80 |
Output signal temperature |
scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer |
Operating range temperature enclosure (°C) |
-35..+70 |
Operating range humidity |
max. 85% rH short term condensation |
Accuracy temperature |
±0,5 K (typ. at 21 °C), within default measuring range, potentiometer for offset adjustment |
Power supply |
15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption |
typ. 0,4 W (24 V =), 0,8 VA (24 V ~) |
Material in touch with media |
Sensor rod, copper, bendable, Ø=4 mm, Sensor neck, stainless steel V4A (1.4571), Ø=6 mm |
Installation length (mm) |
400 |
Enclosure |
USE-S, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour |
pure white |
Protection (IP) |
IP65, according to EN 60529 |
Connection |
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
Delivery content |
incl. mounting clip enclosure USE-S pure white, incl. fixing kit rawlplugs and screws (2x each) |
Packaging length (mm) |
70 |
Packaging width (mm) |
70 |
Packaging height (mm) |
500 |
Packaging |
case packaging |
Device length (mm) |
63 |
Device width (mm) |
68 |
Device height (mm) |
440 |
Standard Manufacturer's Warranty
- Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::