Room operating unit temperature – RS485 Modbus
| Application/type |
Room operating unit |
| Purpose |
Room Climate Control, Measure values |
| Measured values |
temperature |
| Interface |
RS485 Modbus |
| Functions |
temperature control, presence |
| Operating functions |
setpoint adjustment temperature, presence detection |
| Operating elements |
potentiometer (P), labelling {- [scale] +}, button (T), with LED 24 V =, colour configurable via jumpers (7 colours) |
| Configuration |
NOVOSapp, uConfig, BUS, jumper, (depending on type) |
| Input |
1x input for floating contact |
| Network technology |
RS485 Modbus |
| Data transmission |
RTU, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
| Operating range temperature (°C) |
-35..+70 |
| Operating ranges temperature (°C) |
-35..+70 |
| Output signal temperature |
0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C -50..+50 | 0..+50 | -20..+80 | -15..+35 °C |
| Operating range humidity |
max. 85% rH non-condensing |
| Accuracy temperature |
±0,5 K (typ. at 21 °C), within default measuring range |
| Power supply |
15..35 V = SELV, 19..29 V ~ SELV |
| Power consumption |
typ. 0,4 W (24 V =), 0,8 VA (24 V ~) |
| Enclosure |
PC V0 |
| Colour |
pure white, with design cover alu or black, (please specify colour when ordering) |
| Protection (IP) |
IP20, according to EN 60529 |
| Connection |
tool-free mountable spring clamp, max. 1,5 mm², cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top) |
| Mounting |
flush-mounted on standard EU box (Ø=60 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately |
| Delivery content |
incl. adhesive foil for mounting |
| Packaging length (mm) |
115 |
| Packaging width (mm) |
105 |
| Packaging height (mm) |
30 |
| Packaging |
case packaging |
| Device length (mm) |
110 |
| Device width (mm) |
100 |
| Device height (mm) |
23 |
| Notes |
+ surcharge for design cover (mandatory), please select colour, for units with additional sensors, discount group may change |
Standard Manufacturer's Warranty
- Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::
- If not in Description, Available Upon Request