Room operating unit temperature, relative humidity – EnOcean (868 MHz)
Application/type |
Room operating unit |
Purpose |
Room Climate Control, Measure values |
Measured values |
temperature |
Interface |
EnOcean (868 MHz) |
Functions |
temperature control, presence |
Operating functions |
setpoint adjustment temperature, presence detection |
Operating elements |
potentiometer (P), labelling {- [scale] +}, button (T) |
Configuration |
DIP switches |
Radio technology |
EnOcean (IEC 14543-3-10) 868 MHz, transmission power <10 mW, EEP A5-10-05 (4BS) |
Data transmission |
wake up time: 100 sec. (default), or 240 sec. (adjustable by DIP switch), heartbeat cycle: every 10th wakeup, every 100 seconds if the angle of rotation changes >5° (setpoint adjuster), temperature change >0,3 K, immediately on pressing the button, optionally configurable |
Operating range temperature (°C) |
0..+40 |
Operating ranges temperature (°C) |
0..+40 |
Output signal temperature |
scaling according EEP, 0..+40 °C |
Operating range humidity |
max. 85% rH non-condensing |
Accuracy temperature |
±0,4 K (typ. at 21 °C) |
Power supply |
solar cell, maintenance-free internal super cap, use of back-up battery possible for insufficiently lit environments, battery LS14250 (3,6 V) |
Enclosure |
PC V0 |
Colour |
pure white |
Protection (IP) |
IP20, according to EN 60529 |
Mounting |
surface-mounted flat on base using adhesive foil or screws |
Delivery content |
incl. adhesive foil for mounting |
Packaging length (mm) |
115 |
Packaging width (mm) |
105 |
Packaging height (mm) |
30 |
Packaging |
case packaging |
Device length (mm) |
110 |
Device width (mm) |
100 |
Device height (mm) |
23 |
Notes |
+ surcharge for design cover (mandatory), please select colour, Please note our sheet 'Information EasySens® Radio' |
Standard Manufacturer's Warranty
- Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::
- If not in Description, Available Upon Request