Immersion sensor, Duct sensor temperature – Active, 4..20 mA
Application/type |
Immersion sensor, Duct sensor |
Purpose |
Measure values |
Measured values |
temperature |
Interface |
Active, 4..20 mA |
Configuration |
jumper |
Sensor |
SI-Protection against permeation of humidity and mechanical stress (e.g. vibration) |
Operating range temperature (°C) |
-50..+160 |
Operating ranges temperature (°C) |
-50..+160 |
Output signal temperature |
scaling analogue output, 0..+160 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer |
Operating range temperature enclosure (°C) |
-35..+70 |
Operating range humidity |
max. 85% rH short term condensation |
Accuracy temperature |
±0,5 K (typ. at 21 °C), within default measuring range, potentiometer for offset adjustment |
Power supply |
15..24 V = (±10%) SELV |
Power consumption |
max. 0,5 W (24 V =) |
Material in touch with media |
Sensor probe, Ø=8 mm, stainless steel V4A (1.4571), G1/2", suitable for usage in aggressive media |
Installation length (mm) |
450 |
Enclosure |
USE-S, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour |
pure white |
Protection (IP) |
IP65, according to EN 60529 |
Connection |
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
Delivery content |
incl. mounting set (screws and accessories) |
Packaging length (mm) |
400 |
Packaging width (mm) |
130 |
Device length (mm) |
63 |
Device width (mm) |
68 |
Device height (mm) |
490 |
Standard Manufacturer's Warranty
- Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::
- If not in Description, Available Upon Request