Outdoor sensor temperature, relative humidity, absolute humidity, enthalpy, dew point, luminosity, atmospheric pressure – RS485 BACnet, 0..5 V, 0..10 V
| Application/type |
Outdoor sensor |
| Purpose |
Measure values |
| Measured values |
temperature, relative humidity, absolute humidity, enthalpy, dew point, luminosity, atmospheric pressure |
| Interface |
RS485 BACnet, 0..5 V, 0..10 V |
| Configuration |
USEapp, uConfig, BUS, jumper, DIP switches |
| Sensor |
ambient light sensor with precise optical filtering appropriate to the human eye |
| Output voltage |
2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ |
| Network technology |
RS485 BACnet (MS/TP) |
| Operating range temperature (°C) |
-30..+70 |
| Operating ranges temperature (°C) |
-30..+70 |
| Output signal temperature |
scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, adjustable at the transducer, optionally configurable |
| Operating range humidity |
max. 85% rH short term condensation |
| Accuracy temperature |
±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig |
| Measuring range humidity |
0..100% rH non-condensing |
| Accuracy humidity |
±2% between 10..90% rH (typ. at 21 °C), offset setting via app or uConfig |
| Measuring range light |
0..1000 lux (default setting), selectable from 6 ranges 0..200 lux | 0..1000 lux | 0..2 klux | 0..10 klux | 0..20 klux | 0..50 klux |
| Accuracy light |
±5% of measuring range |
| Measuring range atm. pressure (hPa) |
500..1500 hPa |
| Accuracy atmospheric pressure |
±0,5% of measured value |
| Power supply |
15..35 V = SELV, 19..29 V ~ SELV |
| Power consumption |
typ. 0,6 W (24 V =), 1,5 VA (24 V ~) |
| Enclosure |
USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
| Colour |
pure white, translucent cover PC |
| Protection (IP) |
IP65, according to EN 60529 |
| Connection |
removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm² |
| Delivery content |
incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories) |
| Packaging length (mm) |
128 |
| Packaging width (mm) |
100 |
| Packaging height (mm) |
65 |
| Packaging |
case packaging |
| Device length (mm) |
85 |
| Device width (mm) |
84 |
| Device height (mm) |
45 |
Standard Manufacturer's Warranty
- Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::
- If not in Description, Available Upon Request