Duct sensor temperature, relative humidity, absolute humidity, enthalpy, dew point, CO2, VOC, CO2/VOC mix – RS485 BACnet, 0..5 V, 0..10 V
Application/type |
Duct sensor |
Purpose |
Measure values |
Measured values |
temperature, relative humidity, absolute humidity, enthalpy, dew point, CO2, VOC, CO2/VOC mix |
Interface |
RS485 BACnet, 0..5 V, 0..10 V |
Configuration |
USEapp, uConfig, BUS, jumper, DIP switches, each output can be set to get a variable mix of CO2 and VOC by configuration via app or uConfig |
Sensor |
NDIR (non-dispersive, infrared) |
Output voltage |
2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ |
Network technology |
RS485 BACnet (MS/TP) |
Operating range temperature (°C) |
0..+50 |
Operating ranges temperature (°C) |
0..+50 |
Output signal temperature |
scaling analogue output, 0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable |
Operating range humidity |
max. 85% rH short term condensation |
Accuracy temperature |
±0,5 K (typ. at 21 °C), within default measuring range, offset setting via app or uConfig |
Measuring range humidity |
0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable |
Accuracy humidity |
±2% between 10..90% rH (typ. at 21 °C), offset setting via app or uConfig |
Measuring range CO2 |
0..2000 ppm, 0..5000 ppm, optionally configurable |
Accuracy CO2 |
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Measuring VOC (mixed gas) |
heated metal oxide semiconductor |
Power supply |
15..35 V = SELV, 19..29 V ~ SELV |
Power consumption |
max. 2,5 W (24 V =), 4,3 VA (24 V ~) |
Material in touch with media |
Pipe, Ø=19,5 mm, black, length 180 mm |
Installation length (mm) |
180 |
Enclosure |
USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour |
pure white |
Protection (IP) |
IP65, according to EN 60529 |
Connection |
removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm² |
Delivery content |
incl. mounting flange, incl. mounting set (screws and accessories) |
Packaging length (mm) |
87 |
Packaging width (mm) |
87 |
Packaging height (mm) |
250 |
Packaging |
case packaging |
Device length (mm) |
85 |
Device width (mm) |
84 |
Device height (mm) |
225 |
Notes |
mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...), air speed 0,3..12 m/s |