Pendulum sensor, Room sensor temperature, CO2 – Active, 0..5 V, 0..10 V
Application/type |
Pendulum sensor, Room sensor |
Purpose |
Measure values |
Measured values |
temperature, CO2 |
Interface |
Active, 0..5 V, 0..10 V |
Configuration |
jumper |
Sensor |
integrated digital temperature transmitter, NDIR (non-dispersive, infrared) |
Output voltage |
2x 0..10 V or 0..5 V, adjustable via jumper, min. load 10 kΩ |
Operating range temperature (°C) |
0..+50 |
Operating ranges temperature (°C) |
0..+50 |
Operating range humidity |
max. 85% rH short term condensation |
Measuring range CO2 |
0..2000 ppm |
Accuracy CO2 |
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Power supply |
15..35 V = SELV, 19..29 V ~ SELV |
Power consumption |
max. 2,5 W (24 V =), 4,3 VA (24 V ~) |
Material in touch with media |
Sensor head, black, length 126 mm |
Enclosure |
USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour |
pure white |
Protection (IP) |
IP20, enclosure IP65, according to EN 60529 |
Connection |
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable plug-in terminal, max. 2,5 mm² |
Connection cable |
PVC, 0,25 mm², black |
Length connection wire (m) |
5 |
Delivery content |
incl. mounting base enclosure USE-M pure white, incl. mounting set (screws and accessories) |
Packaging length (mm) |
310 |
Packaging width (mm) |
220 |
Device length (mm) |
110 |
Device width (mm) |
105 |
Device height (mm) |
48 |
Option enclosure |
LCD 29x35 mm, RGB backlight |
Standard Manufacturer's Warranty
- Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::
- If not in Description, Available Upon Request