Room operating unit temperature – EnOcean (868 MHz)
Application/type |
Room operating unit |
Purpose |
Room Climate Control, Lighting control, Measure values |
Measured values |
temperature |
Interface |
EnOcean (868 MHz) |
Functions |
temperature control |
Operating functions |
setpoint adjustment, in steps ±1 to ±10 °C, optionally configurable, light ON/OFF |
Operating elements |
4 buttons, labelling {[thermometer] - [thermometer] + [light off] [light on]} |
Configuration |
airConfig, Software/Plug-In for configuration |
Radio technology |
EnOcean (IEC 14543-3-10) 868 MHz, transmission power <10 mW |
Data transmission |
bidirectional, SmartACK (SmartACKNOWLEDGE), wake up time: 240 sec. (default), heartbeat cycle: every 10th wakeup, optionally configurable |
Operating range temperature (°C) |
0..+40 |
Operating ranges temperature (°C) |
0..+40 |
Output signal temperature |
scaling according EEP, 0..+40 °C |
Operating range humidity |
max. 85% rH non-condensing |
Accuracy temperature |
±0,4 K (typ. at 21 °C) |
Power supply |
solar cell, maintenance-free LiPo-battery, use of back-up battery possible for insufficiently lit environments, coin cell CR1632 |
Enclosure |
PC V0 |
Colour |
pure white brilliant |
Protection (IP) |
IP20, according to EN 60529 |
Switch ranges |
Berker, Busch-Jaeger, Feller, Gira, Jung, Merten, (please specify the desired frame when ordering) |
Switch range Berker |
S.1, B.7 glass |
Switch range Busch-Jaeger |
Busch-axcent® with intermediate frame, Busch-balance® SI, future® linear with intermediate frame, solo® with intermediate frame |
Switch range Feller |
EDIZIOdue with intermediate frame, STANDARDdue with intermediate frame |
Switch range Gira |
E2, E3, Esprit, Event, Flächenschalter with intermediate frame, Standard 55 |
Switch range Jung |
A 500, A 550, A creation, A plus, AS 500 |
Switch range Merten |
M-Arc, M-Plan, M-Pure, M-Smart |
Mounting |
surface-mounted flat on base using adhesive foil or screws |
Delivery content |
incl. adhesive foil for mounting |
Packaging length (mm) |
92 |
Packaging width (mm) |
87 |
Packaging height (mm) |
35 |
Packaging |
case packaging |
Device length (mm) |
54 |
Device width (mm) |
54 |
Device height (mm) |
13 |
Weight (g) |
50 |
Notes |
minimum illuminance at standard setting: 200 lx for 8 hours, for configuration an optional programming interface is available, energy storage can be recharged with a separate USB-cable, to use the free software airConfig (download) a USB stick, which is able to send and receive EnOcean telegrams, is necessary. The EnOcean USB stick (incl. license) is included in airScan (item No. 566704 for 868 MHz), (refer to accessories), Please note our sheet 'Information EasySens® Radio' |
Standard Manufacturer's Warranty
- Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::
- If not in Description, Available Upon Request