Room operating unit temperature, relative humidity, absolute humidity, enthalpy, dew point, VOC – KNX (TP)
 
						
			| Application/type | Room operating unit | 
					
			| Purpose | Room Climate Control, Lighting control, Scene control, Shading control, Measure values | 
					
			| Measured values | temperature, relative humidity, absolute humidity, enthalpy, dew point, VOC | 
					
			| Interface | KNX (TP) | 
					
			| Functions | temperature control, fan control, change-over, window/door monitoring, presence, lighting, blinds/shutter | 
					
			| Operating functions | setpoint adjustment temperature, fan stage adjustment, presence detection, light ON/OFF/DIM, blind UP/DOWN/SET, setup scenarios, ECO function, showing measured value and history | 
					
			| Operating elements | touch screen | 
					
			| Configuration | NOVOSapp, uConfig, ETS (KNX) | 
					
			| Input | 1x input for NTC10k or floating contact, 2x input for floating contact | 
					
			| Network technology | KNX (TP1) | 
					
			| Operating range temperature (°C) | 0..+50 | 
					
			| Operating ranges temperature (°C) | 0..+50 | 
					
			| Output signal temperature | 0..+50 °C | 
					
			| Operating range humidity | max. 85% rH non-condensing | 
					
			| Accuracy temperature | ±0,5 K (typ. at 21 °C), within default measuring range | 
					
			| Measuring range humidity | 0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable | 
					
			| Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) | 
					
			| Measuring VOC (mixed gas) | heated metal oxide semiconductor | 
					
			| Power supply | 24 V = (±10%) SELV | 
					
			| Power consumption | typ. 2,5 W (24 V =) | 
					
			| Display | TFT 4,8", 1120x480 px, capacitive touch technology | 
					
			| Enclosure | with thermal separation and sensor channel, PC V0 | 
					
			| Colour | black | 
					
			| Protection (IP) | IP30, according to EN 60529 | 
					
			| Connection | removable plug-in terminal, max. Ø=0,8 mm, cable entry via rear opening | 
					
			| Mounting | flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm), base part can be mounted and wired separately | 
					
			| Packaging length (mm) | 170 | 
					
			| Packaging width (mm) | 110 | 
					
			| Packaging height (mm) | 45 | 
					
			| Packaging | case packaging | 
					
			| Device length (mm) | 146 | 
					
			| Device width (mm) | 90 | 
					
			| Device height (mm) | 41 | 
					
			| Notes | mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...), KNX certification: pending | 
		
        
        
            Standard Manufacturer's Warranty
        
      
         
               - Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::