Room operating unit CO2, temperature, relative humidity – BUS
Application/type |
Room operating unit |
Purpose |
Room Climate Control, Measure values |
Measured values |
temperature, relative humidity, CO2 |
Interface |
RS485 Modbus |
Functions |
presence |
Operating functions |
setpoint adjustment temperature, presence detection, status feedback via LED |
Operating elements |
potentiometer (P), labelling of the manufacturer, button (T) |
Configuration |
BUS, DIP switches |
Sensor |
integrated digital temperature transmitter, NDIR (non-dispersive, infrared) |
Input |
2x input digital for floating switch contact |
Network technology |
RS485 Modbus |
Data transmission |
RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) |
0..+50 |
Operating ranges temperature (°C) |
0..+50 |
Output signal temperature |
0..+50 °C |
Operating range humidity |
max. 85% rH non-condensing |
Accuracy temperature |
±0,5 K (typ. at 21 °C) |
Measuring range humidity |
0..100% rH non-condensing |
Accuracy humidity |
±2% between 10..90% rH (typ. at 21 °C) |
Measuring range CO2 |
0..2000 ppm |
Accuracy CO2 |
±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa) |
Power supply |
15..35 V = SELV, 19..29 V ~ SELV |
Power consumption |
max. 1,6 W (24 V =), 3,9 VA (24 V ~) |
Enclosure |
central disc in design of the manufacturer |
Colour |
pure white matt |
Protection (IP) |
IP30, according to EN 60529 |
Connection |
terminal block, max. 1,5 mm² |
Switch ranges |
Gira |
Switch range Gira |
E2 |
Mounting |
flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm) |
Delivery content |
incl. frame |
Packaging length (mm) |
90 |
Packaging width (mm) |
90 |
Packaging height (mm) |
80 |
Packaging |
case packaging |
Device length (mm) |
81 |
Device width (mm) |
81 |
Device height (mm) |
38 |
Weight (g) |
50 |
Standard Manufacturer's Warranty
- Delivery::
- Worldwide Express Delivery via FEDEX
- Shipping::
- Calculated Before Payment
- Country of Origin::
- EU (Original Part)
- Product Datasheet::
- If not in Description, Available Upon Request